SCB10-315KVA/400KVA/500KVA/630KVA800KVA1000KVA干式电力变压器多少钱一台¥什么价格 一、概述Summary 干式变压器是一种铁芯和绕组不浸于绝缘液体中的变压器。本公司生产的环氧树脂浇注干式变压器产品按IEC国际标准和现行国家标准进行设计,其制造技术先进,具有低损耗、低局放、低噪音的安全、环保型产品。 The dry type transformer is a transformer with an iron core and winding not immersed in the insulating liquid. The company produced epoxy resin casting dry type transformer designs according to IEC international standards and the current national standards, advanced manufacturing technology. It’s safety and environmentally friendly products with low loss, low power, low noise. 二、标准Standards IEC 60076-11 GB 1094.11 GB/T 10228
三、型号含义Type Meaning
四、技术参数Technical Specification
10kV级SC(B)型干式变压器技术参数 Technical Specification of SC(B) type dry-type transformer with 10kV
额定容量 Rated Power (kV•A) | 电压组合 Voltage Combination | 联结组别 Connection Symbol | 空载损耗 No-load Loss (W) | 负载损耗 load Loss (W) (F)(120℃) | 空载电流No-load Current (%) | 短路阻抗Short- circuit Impedance (%) |
| 高压HV (kV) | 高压分接范围Tapping Range of HV (%) | 低压LV (kV) |
| 10型 10Type | 11型 11Type | 12型 12Type |
| 30 | 6 6.3 6.6 or 10 10.5 11 | ±2×2.5 or ±5 | 0.4 | Dyn11 or Yyn0 | 190 | 170 | 150 | 710 | 2.0 | 4.0 |
| 50 | 270 | 240 | 215 | 1000 | 2.0 |
| 80 | 370 | 330 | 295 | 1380 | 1.5 |
| 100 | 400 | 360 | 320 | 1570 | 1.5 |
| 125 | 470 | 420 | 375 | 1850 | 1.3 |
| 160 | 540 | 480 | 430 | 2130 | 1.3 |
| 200 | 620 | 550 | 495 | 2530 | 1.1 |
| 250 | 720 | 640 | 575 | 2760 | 1.1 |
| 315 | 880 | 790 | 705 | 3470 | 1.0 |
| 400 | 980 | 880 | 785 | 3990 | 1.0 |
| 500 | 1160 | 1040 | 930 | 4880 | 1.0 |
| 630 | 1340 | 1200 | 1070 | 5880 | 0.85 |
| 630 | 1300 | 1170 | 1040 | 5960 | 0.85 | 6.0 |
| 800 | 1520 | 1360 | 1210 | 6960 | 0.85 |
| 1000 | 1770 | 1590 | 1410 | 8130 | 0.85 |
| 1250 | 2090 | 1880 | 1670 | 9690 | 0.85 |
| 1600 | 2450 | 2200 | 1960 | 11700 | 0.85 |
| 2000 | 3050 | 2740 | 2440 | 14400 | 0.68 |
| 2500 | 3600 | 3240 | 2880 | 17100 | 0.68 |
|
注:表中数据仅供参考,公司保留数据变动的权力,并接受特殊订货。 Sample data is for reference only. The company reserves the right to change the data, and to accept special orders.
20kV级SC(B)系列干式变压器技术参数 Technical specification of 20kV SC(B) type dry-type transformer
额定容量Rated Power (kV•A) | 电压组合 Voltage Combination | 联结组别 Connection Symbol | 空载损耗 No-load Loss (W) | 负载损耗 load Loss (W) (F)(120℃) | 空载电流No-load Current (%) | 短路阻抗 Short- circuit Impedance (%) | 高压HV (kV) | 高压分接范围Tapping Range of HV (%) | 低压LV (kV) | 50 | 20 22 24 | ±2.5 ±5 | 0.4 | Dyn11 Yyn0 | 340 | 1230 | 2.0 | 6.0 | 100 | 540 | 1990 | 1.8 | 160 | 670 | 2470 | 1.5 | 200 | ±2×2.5 ±5 | 730 | 2940 | 1.5 | 250 | 840 | 3420 | 1.3 | 315 | 970 | 4080 | 1.3 | 400 | 1150 | 4840 | 1.1 | 500 | 1350 | 5790 | 1.1 | 630 | 1530 | 6840 | 1.0 | 800 | 1750 | 8260 | 1.0 | 1000 | 2070 | 9780 | 0.85 | 1250 | 2380 | 11500 | 0.85 | 1600 | 2790 | 13800 | 0.85 | 2000 | 3240 | 16300 | 0.7 | 2500 | 3870 | 19300 | 0.7 |
注:表中数据仅供参考,公司保留数据变动的权力,并接受特殊订货。 Sample data is for reference only. The company reserves the right to change the data, and to accept special orders.
五、外形尺寸图Overall Dimension Drawing 10kV级SC(B)型干式变压器外形尺寸图 Overall dimension drawing of 10kV SC(B) type dry-type transformer |
| 额定容量 Rated Power (kVA) | 尺 寸 Overall Dimension (mm) |
| L | W | H | L* | W* | e | f | g |
|
| 160 | 1500 | 1200 | 2200 | 550 | 660 | 930 | 263 | 330 |
| 200 | 1500 | 1200 | 2200 | 550 | 660 | 940 | 268 | 338 |
| 250 | 1500 | 1200 | 2200 | 550 | 660 | 950 | 273 | 344 |
| 315 | 1500 | 1250 | 2200 | 550 | 660 | 960 | 278 | 350 |
| 400 | 1600 | 1300 | 2200 | 550 | 820 | 970 | 285 | 355 |
| 500 | 1700 | 1350 | 2200 | 660 | 820 | 985 | 295 | 360 |
| 630 | 1700 | 1350 | 2200 | 660 | 820 | 992 | 313 | 377 |
| 800 | 1800 | 1400 | 2200 | 820 | 820 | 1039 | 343 | 388 |
| 1000 | 1900 | 1400 | 2200 | 820 | 820 | 1109 | 351 | 391 |
| 1250 | 1900 | 1500 | 2200 | 820 | 820 | 1177 | 363 | 425 |
| 1600 | 2100 | 1700 | 2200 | 820 | 820 | 1535 | 323 | 390 |
| 2000 | 2300 | 1700 | 2300 | 1070 | 1070 | 1650 | 340 | 410 |
| 2500 | 2300 | 1700 | 2400 | 1070 | 1070 | 1780 | 360 | 430 |
|
注:提供的外形尺寸仅为设计选型时参考,最终尺寸以产品实际尺寸为准。 Note:The overall dimension is only for reference.
品介绍 35kV级SC(B)10干式变压器用于将20kV电网电源直接降低为400V配电电源或10kV输电电源为用户供电。由于具有诸多显著优点,为越来越多的工程所采用。 执行标准 GB6450-1986干式电力变压器 GB/T10228-1997干式电力变压器技术参数和要求 GB/T17211-1998干式电力变压器负载导则 GB1094.3-2003电力变压器第3部分:绝缘水平、绝缘试验和外绝缘空气间隙 JB/T10088-2004 6~500KV级电力变压器声级 JB/T56009-1998干式电力变压器产品质量分等 35kV级SC(B)10干式变压器主要优点有: 1、减少占地和多级变电工程建设,具有显著的社会效益。 2、节省工程投资,提高经济效益。 3、减少10kV输变电环节,使运行维护费用明显降低。 4、采用高压小电流代替低压大电流输电,减少线路损耗,降低线路运行成本。 5、20kV电源直接进入用电中心,有效提高供电的可靠性。 35kV级SC(B)10干式变压器产品特点: 1、高性能、低损耗,为9型系列的换代产品。 2、选用优质硅钢片,同时大幅降低磁通密度,减小运行中硅钢片磁致伸缩量,有效降低噪音。 3、优化高压线圈结构,改善了层间电压和电容的分布,大大提高了产品耐受大气过电压和操作过电压的冲击能力,同时也改善了电场分布,使产品局放量进一步降低。 4、可配置温控系统和风冷装置,在负荷过大时自动启动风机冷却装置,有效提高设备过负荷能力。 35kV级SC(B)10干式变压器技术参数
型号 TYPE | 联结组标号 | 电压组合(KV) | 空载电流 % | 空载损耗 W | 负载损耗 W(120℃) | 短路阻抗 % | 高压KV | 高压分接范围% | 低压KV | SCB10-315/35 | Yyn0 或 Yd11 | 35 或 38.5 | ±5% 或 2×2.5% | 0.4 3.15 6 6.3 10 10.5 11 | 2 | 1160 | 4170 |
| SCB10-400/35 | 2 | 1360 | 5360 |
| SCB10-500/35 | 2 | 1600 | 6590 | 6 | SCB10-630/35 | 1.8 | 1840 | 7680 |
| SCB10-800/35 | 1.9 | 2220 | 9350 |
| SCB10-1000/35 | 1.9 | 2640 | 10880 | 7 | SCB10-1250/35 | 1.7 | 3090 | 12840 |
| SCB10-1600/35 | 1.7 | 3650 | 15390 |
| SCB10-2000/35 | 1.5 | 4200 | 18110 | 8 | SCB10-2500/35 | 1.5 | 4800 | 21680 |
| SCB10-3150/35 | 1.3 | 5000 | 24400 |
| SCB10-4000/35 | 1.3 | 6950 | 29330 | 9 | SCB10-5000/35 | 1.1 | 8320 | 34770 |
| SCB10-6300/35 | 1.1 | 9840 | 40630 |
| SCB10-8000/35 | Yd11 或 Ynd11 | 1 | 11200 | 45050 |
| SCB10-10000/35 | 1 | 12800 | 51200 | 7 | SCB10-12500/35 | 0.9 | 16150 | 55300 | SCB10-16000/35 | 0.8 | 19560 | 59800 |
|